6 Setup with the integrated display and adjustment unit

VEGAMET 625 • Double channel HART

28970-EN-130701

– Jump to next higher menu

Note:

Approx. 10 minutes after the last pressing of a key, an automatic reset

to measured value indication is triggered. Any values not confirmed

with [OK] will not be saved.

6.2 Setup steps

Through parameter adjustment, the instrument is adapted to the indi-

vidual application conditions. A measurement loop calibration is the

most important step and should always be carried out. A scaling of

the measured value to the desired physical variable and unit, possibly

including a linearization curve, is often useful. The adaptation of the

relay switching points or the setting of an integration time to smooth

the measured value are further standard adjustment options.
Instruments with Ethernet interface can be provided with a Host name

suitable for the measurement loop. As an alternative to the addressing

via DHCP, it is also possible to adjust an IP address and subnet mask

suitable for your network. If necessary, the e-mail/Web server can be

also configured with PACTware.
Information:

When using PACTware and the corresponding VEGA DTM, additional

settings can be carried out which are not possible or only partly pos-

sible with the integrated display and adjustment unit. When using an

adjustment software, you either need one of the integrated interfaces

(RS232/Ethernet) or the interface converter VEGACONNECT.
Further instructions for setting up the web server and e-mail functions

are stated in the online help of PACTware or the VEGAMET 625 DTMs

as well as the supplementary instructions manual "RS232/Ethernet

connection".

VEGAMET 625 can process measured values of more than one

HART sensor. The measured values are transmitted as digital HART

signals to the same cable (bus). An analogue 4 … 20 mA transmis-

sion is not possible, the current is limited to 4 mA. An own, unam-

biguous address (address range 1-15) must be assigned to each

connected sensor. This mode is also called HART multidrop mode.

Address 0 (mode 4 … 20 mA) must not be used.
Note:

When addresses are being assigned, only one sensor must be con-

nected on the bus. If this is not the case, no sensor can be accessed

and it is not possible to assign an address.
The addressing can be carried out directly on each HART sensor via

the respective adjustment unit or adjustment software. As an alterna-

tive, the setting of the sensor address can be also carried out via the

VEGAMET menu under "Service - Sensor address" (see chapter

"Setup procedure" under "Service - Change sensor address").

Parameter adjustment

Set HART address