6 Setup with the integrated display and adjustment unit

VEGAMET 625 • Double channel HART

28970-EN-130701

Enter the requested parameters via the appropriate keys and

save your settings with [OK].

A linearization is necessary for all vessels in which the vessel volume

does not increase linearly with the level, for example, with a cylindrical

or spherical tank. Corresponding linearization curves are prepro-

grammed for these vessels. They represent the correlation between

the level percentage and vessel volume. By activating the appropriate

curve, the volume percentage of the vessel is displayed correctly. If

the volume should not be displayed in percent but e.g. in l or kg, a

scaling can be also set.

Enter the requested parameters via the appropriate keys and

save your settings with [OK].

Scaling means converting the measured value into a certain param-

eter and unit. The linearized percentage value is the source signal

which is used as basis for the scaling. The indication can then show

the volume in litres e.g., instead of the percentage value. Indication

values from max. -99999 to +99999 are possible.

Enter the requested parameters via the appropriate keys and

save your settings with [OK].

In this menu item you can enter an unambiguous designation for each

measurement loop, e.g. the measurement loop name or the tank or

product designation. In digital systems and in the documentation

of larger plants, a singular designation should be entered for exact

identification of individual measuring points.

Enter the requested parameters via the appropriate keys and

save your settings with [OK].

Under "Outputs" you will find the relay/current outputs. With relay

output, first of all the requested mode ("Overfill protection" or "Dry

running protection") must be selected.

Meas. loop - Linearization

curve

Meas. loop - Scaling

Meas. loop - Meas. loop

TAG

Meas. loop - Outputs -

Relays outputs