6 Setup with the integrated display and adjustment unit

VEGAMET 625 • Double channel HART

28970-EN-130701

Overfill protection: Relay is switched off when the max. level is

exceeded (safe currentless condition), relay is switched on again

when the level falls below the min. level (switch-on point < switch-

off point)

Dry run protection: Relay is switched off when the level falls

below the min. level (safe currentless condition), relay is switched

on again when the max. level is exceeded (switch-on point >

switch-off point)

Additional modes such as "Switching window", "Flow" and "Tenden-

cy" can be only adjusted via PACTware and DTM.

Select the requested mode and save with [OK]. By pushing [->], you

reach the next menu item.
1. Now enter the reference value to which the relay switching points

relate. By pushing [->], you reach the next menu item.

2. Enter now the switching points for switching the relay on and off.

The parameter to which they refer can also be selected.

In the following window the reaction of the relay in case of failure can

be determined. Here you can define whether, in case of failure, the

switching condition of the relay remains unchanged or the relay is

switched off.

The current output is used to transfer the measured value to a higher

ranking system, for example to a PLC, a control system or a meas-

ured value indication. This is an active output, i.e. a current is provided

actively. The processing unit must hence have a passive current input.
The characteristics of the current outputs can be set to 0 … 20 mA,

4 … 20 mA or inverted. The reaction in case of failure can be also

adapted to the requirements. The parameter to which they refer can

also be selected.

Meas. loop - Outputs -

Current outputs