8 Application examples

VEGAMET 625 • Double channel HART

28970-EN-130701

Depending on the type and version, each flume generates a different

backwater. The data of the following flumes are available in the instru-

ment:

Palmer-Bowlus-Flume

Venturi flume, trapezoidal weir, rectangular weir

Rectangular weir, V-Notch

Setup

The configuration of the flow measurement loop requires PACTware

with the suitable DTMs. The example refers to a flow measurement

with a radar sensor. The following setup steps must be carried out:

Selection of the parameter "Flow"

Carrying out adjustment

Select flume (linearization)

Set scaling

Parameter adjustment of pulse outputs

Select in the DTM window "Parameter" the option "Flow" with the

requested unit of measurement.

Min. adjustment: Enter the suitable value for 0 %, i.e. the distance

from the sensor to the medium as long as there is no flow. These are

in the following example 1.40 m.
Max. adjustment: Enter the suitable value for 100 %, i.e. the distance

from the sensor to the medium, with the max. flow volume. This is

0.80 m in the following example.

100%

0,80m (d)

=

400m

3

/h

=

0%

1,40m (d)

=

0m

3

/h

=

Fig. 16: Adjustment of flow measurement with V-notch

Select in the DTM window "Linearization" the option "Flow" and then

the used flume (in the above example V-notch).

Select in the DTM window "Scaling" under "Parameter" the option

"Flow". Finally the allocation of a value must be carried out, i.e. the

flow volume is assigned to the 0 and 100 % value. As the last step,

select the requested meas. unit. For above example: 0 % = 0 and

100 % = 400, meas. unit m³/h.

Flume

Parameter - Flow

Adjustment

Linearization curve

Scaling