2 mounting preparations – VEGA VEGASON 65 Profibus PA User Manual

Page 13

Advertising
background image

1

3

2

100%

0%

4

Fig. 4: Version B, C, D - Measuring range (operating range) and max. measuring
distance
1

full (dead band)

2

empty (max. measuring distance)

3

Measuring range

4

Reference plane

Gauge pressure in the vessel does not influence VEGASON 65. Low
pressure or vacuum does, however, damp the ultrasonic pulses. This
influences the measuring result, particularly if the level is very low.
With pressures under -0.2 bar (-20 kPa) you should use a different
measuring principle, e.g. radar or guided microwave.

4.2 Mounting preparations

Warning:
Mounting preparations must be carried out in idle condition. Non-
observance can cause damages on the electronics!

Version B is supplied in two parts:

l

Transducer

l

Electronics housing

Assemble the version as follows:

1

Loosen the screws on the fixing ring (4) with a hexagon spanner
(size 4), remove the transducer tube out of the swivelling holder

2

Mount the flange

Pressure/Vacuum

Mounting - Version B

VEGASON

65 • Profibus PA

13

4 Mounting

28788

-

EN

-081127