2 principle of operation, 3 operation – VEGA VEGAPULS 66 (≥ 2.0.0 - ≤ 3.8) standpipe ver. 4 … 20 mA_HART four-wire User Manual

Page 10

Advertising
background image

3.2 Principle of operation

VEGAPULS

66

is a radar sensor in C-band (emitting frequency

approx. 6 GHz) for continuous level measurement.

A

special version of VEGAPULS 66 is available for each area of

application. The version with flange and standpipe is particularly
suitable for the measurement of solvents and liquid gases.

T

he standpipe antenna is also suitable for vessels with foam

generation or for measurement of products with low dielectric figures
(DK > 1.6).

M

easurement in a standpipe is not recommended for very adhesive

products.

F

or pressures up to 160 bar (2320 psi) and temperatures up to 400 °C

(752 °F)

there are graphite seals and ceramic antenna cones

available.

T

he antenna of the radar sensor emits short radar pulses with a

duration of approx. 1 ns. These pulses are reflected by the product
and received by the antenna as echoes. The running time of the radar
pulses from emission to reception is proportional to the distance and
hence to the level. The determined level is converted into an
appropriate output signal and outputted as measured value.

F

our-wire electronics with separate power supply.

T

he supply voltage range can differ depending on the instrument

version.

T

he data for power supply are specified in chapter "Technical data".

M

easured value transmission is carried out via the 4 … 20 mA/HART

output separate from power supply.

T

he background lighting of the indicating and adjustment module is

powered by the sensor. A certain level of operating voltage is required
for this. You can find the exact voltage specifications in chapter
"

Technical data".

3.3 Operation

VEGAPULS

66

can be adjusted with different adjustment media:

l

with indicating and adjustment module

l

with the suitable VEGA DTM in conjunction with an adjustment
software according to the FDT/DTM standard, e.g. PACTware and
PC

l

with manufacturer-specific adjustment programs AMS™ or PDM

l

W

ith a HART handheld

T

he entered parameters are generally saved in VEGAPULS 66,

optionally also in the indicating and adjustment module or in
PACT

ware.

Application area

Functional principle

Power supply

10

VEGAPULS

66

standpipe version • 4 … 20 mA/HART four-wire

3 P

roduct description

28742

-EN

-090305

Advertising