VEGA VEGAPULS 66 (≥ 2.0.0 - ≤ 3.8) standpipe ver. 4 … 20 mA_HART four-wire User Manual

Page 34

Advertising
background image

N

ecessary components:

l

VEGAPULS

66

l

PC

with PACTware and suitable VEGA DTM

l

VEGACONNECT

l

P

ower supply unit or processing system

2

3

1

4

5

Power supply

VEGACONNECT 3

PACTware /

TM

Fig. 16: Connecting the PC via HART to the signal cable

1

RS232 connection

2

VEGAPULS 66

3

HART adapter cable for VEGACONNECT 3

4

HART resistor 250 Ω

5

4 … 20 mA processing

N

ecessary components:

l

VEGAPULS

66

l

PC

with PACTware and suitable VEGA DTM

l

VEGACONNECT

3

with HART adapter cable

l

HART

resistor 250 Ω

l

P

ower supply

l

4 … 20

mA processing

Note:
F

or processings with integrated HART resistance (inner resistance

approx. 250 Ω), there is no additional, external resistance necessary.
I

n such cases, VEGACONNECT 3 can be connected in parallel to the

4 … 20

mA cable.

Connection via HART

34

VEGAPULS

66

standpipe version • 4 … 20 mA/HART four-wire

7 S

etup with PACTware and other adjustment programs

28742

-EN

-090305