VEGA VEGAPULS 63 (≥ 2.0.0 - ≤ 3.8) Profibus PA User Manual

Page 34

Advertising
background image

Information:
With VEGAPULS 63 with electronics version "Increased safety",
"

Solid" is preset as factory setting. However, the instrument should be

used preferably in liquids. In such cases, the medium selection should
be set to "Liquid" during setup.

According to the conductivity and the dielectric figure of liquids, the
reflection properties can differ considerably. Therefore additional
options such as "Solvent", "Chem. mixture" and "Water based" are
offered below the menu item Liquid.

With solids, you can also choose between "Powder/Dust", "Granular/
Pellets
" or "Ballast/Pebbels".

Through this additional selection, the sensor is adapted perfectly to the
product and measurement reliability, particularly in products with poor
reflective properties, is considerably increased.

Enter the requested parameters via the appropriate keys, save your
settings and jump to the next menu item with the [->] key.

Apart from the medium, the vessel shape can also influence the
measurement. To adapt the sensor to these measuring conditions, this
menu item offers different options depending on whether liquid or bulk
solid is selected. With "Liquids" these are "Storage tank", "Stilling
tube
", "Open vessel" or "Stirred vessel", with "Solid", "Silo" or
"

Bunker".

Vessel form

Storage tank

Information:
With VEGAPULS 63 with electronics version "Increased safety",
"

Solid" is preset as factory setting. However, the instrument should be

used preferably in liquids. In such cases, the vessel form should be set
to "Storage tank" during setup.

Enter the requested parameters via the appropriate keys, save your
settings and jump to the next menu item with the [->] key.

A linearisation is necessary for all vessels in which the vessel volume
does not increase linearly with the level - e.g. in a horizontal cylindrical
or spherical tank - and the indication or output of the volume is
required. Corresponding linearisation curves are preprogrammed for
these vessels. They represent the correlation between the level
percentage and vessel volume. By activating the appropriate curve,
the volume percentage of the vessel is displayed correctly. If the
volume should not be displayed in percent but e.g. in l or kg, a scaling
can be also set in the menu item "Display".

Vessel form

Linearisation curve

34

VEGAPULS

63 • Profibus PA

6 Set up with the indicating and adjustment module PLICSCOM

28446

-EN

-120530