VEGA VEGAPULS 63 (≥ 2.0.0 - ≤ 3.8) Profibus PA User Manual

Page 56

Advertising
background image

Module of the PA sensors
For the cyclic data traffic, VEGAPULS 63 provides the following modules:

l

AI (PA-OUT)

-

PA-OUT value of the FB1 after scaling

l

Additional Cyclic Value

-

Additional cyclical value (depending on the source)

l

Free Place

-

This module must be used if a value in the data telegram of the cyclical data traffic should not be
used (e.g. replacement of temperature and Additional Cyclic Value)

Max. two modules can be active. By means of the configuration software of the Profibus master, you
can determine the configuration of the cyclical data telegram with these modules. The procedure
depends on the respective configuration software.

Note:
The modules are available in two versions:

l

Short for Profibus master supporting only one "Identifier Format"
byte, e.g. Allen Bradley

l

Long for Profibus master only supporting the "Identifier Format"
byte, e.g. Siemens S7-300/400

Examples of telegram configuration
In the following you will see how the modules can be combined and how the appendant data telegram
is structured.

Example 1 (standard setting) with distance value and additional cyclical value:

l

AI (PA-OUT)

l

Additional Cyclic Value

Byte-No.

1

2

3

4

5

6

7

8

9

10

Status

Status

Status

Status

(FB1)

IEEE-754-

Floating point value

PA-OUT

(FB1)

IEEE-754-

Floating point value

Additional Cyclic

Value

Format

Value

Example 2 with distance value without additional cyclical value:

l

AI (PA-OUT)

56

VEGAPULS

63 • Profibus PA

10 Annex

28446

-EN

-120530