VEGA VEGAPULS 68 (≥ 2.0.0 - ≤ 3.8) Profibus PA User Manual

Page 39

Advertising
background image

4

Enter the suitable distance value in m for the empty vessel (e.g.
distance from the sensor to the vessel bottom) corresponding to
the percentage value.

5

Save the settings with [OK] and move to "Max. adjustment" with [-
>

]

.

Proceed as follows:

Max. adjustment

100.00 %

=

1.000 m(d)

2.000 m(d)

1

Prepare the % value for editing with [OK] and set the cursor to the
requested position with [->]. Set the requested percentage value
with [+] and save with [OK]. The cursor jumps now to the distance
value.

2

Enter the appropriate distance value in m (corresponding to the
percentage value) for the full vessel. Keep in mind that the max.
level must lie below the dead band.

3

Save the settings with [OK] and move to "Medium selection" with
[->]

.

Each product has different reflective properties. In solids, these are
dust generation, material cones and additional echoes caused by the
vessel wall. Due to the medium selection, the sensor is adapted in an
optimum way to the product and the accuracy, particularly for products
with bad reflective properties, is increased considerably.

Medium

Bulk solid

With solids, you can also choose between "Powder/Dust", "Granular/
Pellets
" or "Ballast/Pebbels".

In liquids, fluctuating surfaces and foam generation are further
interfering factors. To adapt the sensor to the different conditions, a
general selection is made in this menu item, i.e. "Solid" or "Liquid".

Enter the requested parameter via the appropriate keys, save your
settings and jump to the next menu item with the [->] key.

Apart from the medium, the vessel shape can also influence the
measurement. To adapt the sensor to these measuring conditions, this
menu item offers different options depending on whether liquid or solid
is selected. With "Solid" these are "Silo" or "Bunker", with "Liquid",
"

Storage tank", "Stilling tube", "Open vessel" or "Stirred vessel".

Carrying out max. ad-
justment

Medium selection

Vessel form

VEGAPULS

68 • Profibus PA

39

6 Set up with the indicating and adjustment module PLICSCOM

29263

-EN

-090305