VEGA VEGAPULS 68 (≥ 2.0.0 - ≤ 3.8) Profibus PA User Manual

Page 55

Advertising
background image

Current value

10 mA, ±0.5 mA

Damping (63 % of the input variable)

0 … 999 s, adjustable

Input variable

Measured value

distance between process fitting and product sur-
face

Max. measuring range

70 m (229.7 ft)

Min. distance from antenna end

400 mm (15.75 in)

Reference conditions to measuring accuracy (similar to DIN EN 60770-1)

Reference conditions according to DIN EN 61298-1

-

Temperature

+

18 … +30 °C (+64 … +86 °F)

-

Relative humidity

45 … 75 %

-

Air pressure

860 … 1060 mbar/86 … 106 kPa (12.5 … 15.4 psig)

Other reference conditions

-

Reflector

ideal reflector, e.g. metal plate 2 x 2 m

-

False reflections

Biggest false echo, 20 dB smaller than the useful
echo

Characteristics and performance data

Frequency

K-band

Interval

approx. 1 s

Beam angle -3 dB with horn antenna, depending on antenna diameter

-

ø

40 mm (1.575 in)

22°

-

ø

48 mm (1.89 in)

18°

-

ø

75 mm (2.953 in)

10°

-

ø

95 mm (3.74 in)

Beam angle -3 dB with parabolic antenna

Step response or adjustment time

6)

>

1 s (dependent on the parameter setting)

Max. level change

Adjustable up to 1 m/min. (dependent on the
parameter adjustment)

Max. emitted HF power of the antenna system

-

Pulse peak power

<

10 mW

-

Pulse duration

<

2 ns

-

Average power

<

25 µW

-

Average power with 1 m distance

<

1 µW/cm

2

6)

Time to output the correct level (with max. 10 % deviation) after a sudden
level change.

VEGAPULS

68 • Profibus PA

55

10 Supplement

29263