5 setup, 5setup – VEGA VEGACAL series 60 User Manual

Page 9

Advertising
background image

5

Setup

5

.1 Setup - Electronics 4 … 20 mA, Profibus PA,

Foundation Fieldbus

If you have ordered the electronics module by stating the sensor
serial number
, it is ready for operation after installation and
connection to power supply.

If you have ordered the electronics module without stating the
sensor serial number
or you are using a suitable electronics module
from stock, you first have to load the sensor data after installation.

In general, the sensor with the new electronics module is ready for
operation. However, the sensor name is "VEGACAL 62" (presetting)
and the serial number is not entered correctly.

If these specifications should be correct, you have to enter the serial
number.

Move via www.vega.com to the item "serial number search". After
entering the serial number, the order data of the sensor are displayed.
The serial number is also available directly from VEGA.

Below the order data you will find "Sensor data for Service-DTM" as
XML file. Load this file with "Save as" on your PC and transfer it then
via PACTware and the Service DTM to the sensor.

As a rule, settings already carried out on site with the previous
electronics module such as min./max. adjustment etc., however must
be repeated.

Tip:
Simply use the copy function of the adjustment module PLICSCOM or
the adjustment software PACTware.

5

.2 Setup - electronics with signal conditioning

instrument

Set all adjustment elements on the new electronics module to the
settings of the old module.

Since the electronics modules are slightly different (approx. 5 %), it
can be necessary to carry out an adjustment on the signal conditioning
instrument after having exchanged the electronics.

With sensor serial num-
ber

Without sensor serial
number

Load sensor data

Adjustment

Adjustment

Electronics module • VEGACAL series 60

9

5 Setup

30531

-

EN

-110411

Advertising