o not mount the instruments in or above the filling stream. Make sure
that you detect the product surface, not the inflowing product.
Fig. 7: Inflowing liquid
T
he socket piece should be dimensioned in such a way that the
antenna end protrudes at least 10 mm (0.4 in) out of the socket.
ca.
10 mm
Fig. 8: Recommended socket mounting
A
lign the sensor in liquids as vertical as possible to the product surface
to achieve optimum measurement.
Inflowing medium
Socket
Sensor orientation