VEGA VEGAPULS 66 (≥ 2.0.0 - ≤ 3.8) enamel 4 … 20 mA_HART two-wire User Manual

Page 16

Advertising
background image

D

o not mount the instruments in or above the filling stream. Make sure

that you detect the product surface, not the inflowing product.

Fig. 7: Inflowing liquid

T

he socket piece should be dimensioned in such a way that the

antenna end protrudes at least 10 mm (0.4 in) out of the socket.

ca.

10 mm

Fig. 8: Recommended socket mounting

A

lign the sensor in liquids as vertical as possible to the product surface

to achieve optimum measurement.

Inflowing medium

Socket

Sensor orientation

16

VEGAPULS

66

enamel • 4 … 20 mA/HART two-wire

4 M

ounting

31953

-EN

-090305

Advertising