Reference conditions to measuring accuracy (similar to DIN EN 60770-1)

R

eference conditions according to DIN EN 61298-1

-

T

emperature

+

18 … +30 °C (+64 … +86 °F)

-

R

elative humidity

45 … 75 %

-

A

ir pressure

860 … 1060

mbar/86 … 106 kPa (12.5 … 15.4 psig)

O

ther reference conditions

-

R

eflector

ideal reflector, e.g. metal plate 2 x 2 m

-

F

alse reflections

B

iggest false echo, 20 dB smaller than the useful

echo

Characteristics and performance data

F

requency

C-

band (6 GHz technology)

B

eam angle 3 dB, depending on the antenna system

-

ø

145

mm (DN 150)

20°

-

ø

195

mm (DN 200)

17°

S

tep response or adjustment time

3)

>

1

s (dependent on the parameter setting)

M

ax. level change

adjustable up to 1 m/min. (dependent on the
parameter adjustment)

M

ax. emitted HF power of the antenna system

-

P

ulse peak power approx.

0.1

mW

-

P

ulse duration

<

2

ns

-

SAR

value

4)

0.471

mW/kg

Measuring accuracy

R

esolution, general

max. 1 mm (0.039 in)

D

eviation

5)

see diagrams

3)

T

ime to output the correct level (with max. 10 % deviation) after a sudden

level change.

4)

at the aperture of a horn antenna with ø 150 mm

5)

I

ncl. non-linearity, hysteresis and non-repeatability.

VEGAPULS

66

enamel • 4 … 20 mA/HART two-wire

51

10 S

upplement

31953

-EN

-090305