Fig. 13: VEGAPULS 66 in a bypass tube. The polarisation marking on the
process fitting must be in one plane with the tube holes or the tube connection
openings.

1

Marking of the polarisation direction

W

hen the sensor is mounted on a bypass tube, the distance from

VEGAPULS

66

to the upper tube connection should be approx.

500

mm (19.69 in) or more. In case of extremely rough tube inner

walls, you should use an inserted tube (tube in tube) or a radar sensor
with tube antenna.

Information:
W

ith VEGAPULS 66 in flange version, the polarisation plane is always

in the center between two flange holes.