VEGA VEGAPULS 66 (≥ 2.0.0 - ≤ 3.8) enamel 4 … 20 mA_HART two-wire User Manual

Page 38

Advertising
background image

Menu item

Reset value

V

essel form

not known

D

amping

0

s

L

inearisation

linear

S

ensor-TAG

S

ensor

D

isplayed value

D

istance

E

xtended settings

N

one

C

urrent output - characteristics

4 … 20

mA

C

urrent output - max. current

20

mA

C

urrent output - min. current

4

mA

C

urrent output - failure

<

3.6

mA

U

nit of measurement

m(d)

T

he values of the following menu items are not reset to the reset

values (see chart) with "Reset":

Menu item

Reset value

L

ighting

no reset

L

anguage

no reset

SIL

no reset

HART

mode

no reset

Factory setting
L

ike basic adjustment, furthermore special parameters are reset to

default values.

2)

Pointer
T

he min. and max. distance values are reset to the actual value.

A

dditional adjustment and diagnosis options such as e.g. scaling,

simulation or trend curve presentation are shown in the following menu
schematic. You will find a detailed description of these menu items in
the operating instructions manual "Indicating and adjustment module".

2)

S

pecial parameters are parameters which are set customer-specifically on

the service level with the adjustment software PACTware.

Optional settings

38

VEGAPULS

66

enamel • 4 … 20 mA/HART two-wire

6 S

et up with the indicating and adjustment module PLICSCOM

31953

-EN

-090305