5 Connecting to power supply

5.1 Preparing the connection

Always keep in mind the following safety instructions:

l

Connect only in the complete absence of line voltage

l

If voltage surges are expected, overvoltage arresters should be
installed according to Profibus specifications

Tip:
We recommend VEGA overvoltage arrester B63-32.

In hazardous areas you must take note of the respective regulations,
conformity and type approval certificates of the sensors and power
supply units.

Power is supplied via a Profibus DP/PA segment coupler or a
VEGALOG

571 EP input card. The power supply range can differ

depending on the instrument version.

The data for power supply are specified in chapter "Technical data".

Connection is made with screened cable according to the Profibus
specification. Power supply and digital bus signal are carried over the
same two-wire connection cable.

Use cable with round cross-section. A cable outer diameter of 5 … 9 mm
(0.2 … 0.35 in) ensures the seal effect of the cable gland. If you are
using cable with a different diameter or cross-section, exchange the
seal or use a suitable cable gland.

Please make sure that your installation is carried out according to the
Profibus specification. In particular, make sure that the termination of
the bus is done with appropriate terminating resistors.

On the instrument with cable entry ½ NPT and plastic housing there is
a metallic ½" threaded insert moulded into the plastic housing.

Caution:
No grease should be used when screwing the NPT cable gland or
steel tube into the threaded insert. Standard grease can contain
additives that corrode the connection between threaded insert and
housing. This would influence the stability of the connection and the
tightness of the housing.

With systems with potential equalisation, connect the cable screen
directly to ground potential at the power supply unit, in the connection
box and at the sensor. The screen in the sensor must be connected
directly to the internal ground terminal. The ground terminal outside on
the housing must be connected to the potential equalisation (low
impedance).

Safety instructions

Voltage supply

Connection cable

Cable gland ½ NPT

Cable screening and
grounding

VEGAFLEX

67 • Profibus PA

15

5 Connecting to power supply

31855

-

EN

-120329