VEGA VEGAFLEX 67 (-40…+150°C) Profibus PA User Manual

Page 47

Advertising
background image

TS

d1

h1

h2

d2

1

L2

L1

Fig. 20: Interface measurement (interface is between L1 and L2)

1

Reference plane

d1 Distance to the interface (Secondary Value 2)
d2 Distance to the level (Distance Level)
TS

Thickness of the upper medium (d1 - d2)

h1 Height - interface (Secondary Value)
h2 Height - Level
L1

Lower medium

L2

Upper medium

Resolution, digital

>

1 mm (0.039 in)

Accuracy (according to DIN EN 60770-1)

Process reference conditions according to DIN EN 61298-1

-

Temperature

+

18 … +30 °C (+64 … +86 °F)

-

Relative humidity

45 … 75 %

-

Air pressure

+

860 … +1060 mbar/+86 … +106 kPa

(+12.5 … +15.4 psig)

-

Emulsion phase

<

2 mm (< 0.079 in)

Installation reference conditions

-

Min. distance to installations

>

500 mm (19.69 in)

-

Vessel

metallic, ø 1 m (3.281 ft), centric installation,
process fitting flush with the vessel ceiling

-

Medium

Water/Oil (dielectric figure ~2.0)

-

Installation

Probe end does not touch the vessel bottom

Sensor parameter adjustment

Gating out of false signals carried out

Deviation

see diagrams
The accuracy values of the diagrams refer to the

VEGAFLEX

67 • Profibus PA

47

10 Supplement

31855

-

EN

-120329