2 principle of operation – VEGA VEGAFLEX 67 (-40…+150°C) Profibus PA User Manual

Page 8

Advertising
background image

l

Serial number

l

Technical data

l

Article numbers, documentation

With the serial number, you can access the delivery data of the
instrument via www.vega.com, "VEGA T

ools" and "serial number

search". In addition to the type label outside, you can also find the
serial number on the inside of the instrument.

3.2 Principle of operation

VEGAFLEX

67 is a level sensor with coax, rod or cable probe for

continuous interface measurment.

It is designed for industrial use in all areas of process technology and
can be used in liquids.

High frequency microwave impulses are guided along a steel cable or
rod or a rod inside a steel tube. When reaching the product surface, a
part of the microwave impulses is reflected. The other part passes the
upper product and is reflected a second time by the interface. The
running times to the two product layers are processed by the
instrument.

Upper medium (L2)

l

The upper medium must not be conductive

l

The dielectric figure of the upper medium must be known (input
required). Min. dielectric figure: rod version 1.7; coax version 1.4.
You can find a list with the dielectric figures on our home page:
www.vega.com

l

The composition of the upper medium must be stable, no varying
products or mixtures

l

The upper medium must be homogeneous, no stratifications within
the medium

l

Min. thickness of the upper medium 100 mm

l

Clear separation from the lower medium, no emulsion phase, no
mull layer

l

If possible, no foam on the surface

Lower medium (L1)

l

The dielectric figure must be 10 higher than the dielectric figure of
the upper medium, preferably electrically conductive. Example:
upper medium dielectric figure 2, lower medium at least dielectric
figure 12

Application range

Functional principle

Prerequisites for inter-
face measurement

8

VEGAFLEX

67 • Profibus PA

3 Product description

31855

-EN

-120329

Advertising