VEGA VEGAFLEX 61 4 … 20 mA_HART two-wire User Manual

Page 34

Advertising
background image

Basic adjustment
I

f the function "Reset" is carried out, the sensor resets the values of the

following menu items to the reset values (see chart):

1)

T

he following values will be reset:

Function

Reset value

M

ax. adjustment

D

istance, upper dead zone

M

in. adjustment - Rod/Coax version

D

istance, supplied sensor length

M

in. adjustment - Cable version

D

istance, lower dead zone

D

amping ti

0

s

L

inearisation

linear

S

ensor-TAG

S

ensor

D

isplay

D

istance

C

urrent output - characteristics

4 … 20

mA

C

urrent output - max. current

20

mA

C

urrent output - min. current

4

mA

C

urrent output - failure

<

3.6

mA

A

pplication - rod/coax version

L

iquid

A

pplication - Cable version

B

ulk solid

T

he values of the following menu items are not reset to the reset

values (see chart) with "Reset":

Menu item

Reset value

L

ighting

no reset

L

anguage

no reset

SIL

no reset

HART

mode

no reset

Factory setting
L

ike basic adjustment, in addition, special parameters are reset to

default values.

2)

Pointer
T

he min. and max. values are reset to the actual value.

A

dditional adjustment and diagnosis options such as e.g. scaling,

simulation or trend curve presentation are shown in the following menu
schematic. You will find a detailed description of these menu items in
the operating instructions manual "Indicating and adjustment module".

1)

S

ensor-specific basic adjustment.

2)

S

pecial parameters are parameters which are set customer-specifically on

the service level with the adjustment software PACTware.

Reset

Optional settings

34

VEGAFLEX

61 • 4 … 20

mA/HART two-wire

6 S

et up with the indicating and adjustment module PLICSCOM

31833

-EN

-100426