VEGA VEGAFLEX 67 (-200…+400°C) Foundation Fieldbus User Manual

Page 49

Advertising
background image

Electromechanical data - version IP 66/IP 67 and IP 66/IP 68; 0.2 bar

Cable entry/plug

4)

-

Single chamber housing

l

1 x cable gland M20 x 1.5 (cable: ø 5 … 9 mm),
1 x blind stopper M20 x 1.5

or:

l

1 x closing cap M20 x 1.5; 1 x blind stopper
M

20 x 1.5

or:

l

1 x closing cap ½ NPT, 1 x blind plug ½ NPT

or:

l

1 x plug (depending on the version), 1 x blind
stopper M20 x 1.5

-

Double chamber housing

l

1 x cable entry M20 x 1.5 (cable: ø 5 … 9 mm),
1 x blind stopper M20 x 1.5; 1 x blind stopper
M

16 x 1.5 or optionally available with 1 x plug

M

12 x 1 for external indicating and adjustment

unit

or:

l

1 x closing cap ½ NPT, 1 x blind stopper
½ NPT

,

1 x blind stopper M16 x 1.5 or

optionally 1 x plug M12 x 1 for external
indicating and adjustment unit

or:

l

1 x plug (depending on the version), 1 x blind
stopper M20 x 1.5; 1 x blind stopper M16 x 1.5
or optionally available with 1 x plug M12 x 1 for
external indicating and adjustment unit

Spring-loaded terminals for wire cross-sec-
tion

<

2.5 mm² (AWG 14)

Electromechanical data - version IP 66/IP 68 (1 bar)

Cable entry

-

Single chamber housing

1 x IP 68 cable gland M20 x 1.5; 1 x blind stopper
M

20 x 1.5

-

Double chamber housing

1 x IP 68 cable gland M20 x 1.5; 1 x blind stopper
M

20 x 1.5; 1 x blind stopper M16 x 1.5

Connection cable

-

Wire cross-section

0.5 mm² (AWG 20)

-

Wire resistance

<

0.036 Ω/m

-

Tensile strength

<

1200 N (270 lbf)

-

Standard length

5 m (16.4 ft)

-

Max. length

1000 m (3280 ft)

4)

Depending on the version M12 x 1, according to DIN 43650, Harting, 7/
8" FF.

VEGAFLEX

67 • Foundation Fieldbus

49

10 Supplement

32314

-

EN

-120329