VEGA VEGAFLEX 65 Profibus PA User Manual
Page 27
l
PA scaling unit
l
PV-Out-Scale
l
Channel
l
Additional PA value
The following safety-relevant data are not read out or written:
l
Sensor address
l
PIN
l
Sensor length/Sensor type
l
False signal suppression
Copy sensor data
Copy sensor data?
Basic adjustment
If the function "Reset" is carried out, the sensor resets the values of the
following menu items to the reset values (see chart):
2)
The following values will be reset:
Function
Reset value
Max. adjustment
Distance, upper dead zone
Min. adjustment
Distance, supplied sensor length
Min. adjustment - Cable version
Distance, lower dead zone
Damping ti
0 s
Linearisation
Linear
Sensor-TAG
Sensor
Display
PA-Out 1
Channel (PV)
lin %
Additional PA value (PV)
lin %
Out-Scale-Unit
%
PV-Out-Scale
0.00 lin % = 0.0 %
100.0 lin % = 100 %
The values of the following menu items are not reset to the reset
values (see chart) with "Reset":
2)
Sensor-specific basic adjustment.
Reset
VEGAFLEX
65 • Profibus PA
27