VEGA VEGAFLEX 65 Profibus PA User Manual
Page 41
Input variable
Measured variable
Level of liquids
Min. dielectric figure of the medium
ε
r
>
1.4
2
4
5
3
1
2
4
5
3
1
Fig. 16: Measuring ranges of VEGAFLEX 65
1
Reference plane
2
Probe length L
3
Measuring range (default setting refers to the measuring range in water)
4
Upper dead band (see diagrams under Accuracy - grey section)
5
Lower dead band (see diagrams under Accuracy - grey section)
Output variable
Output signal
digital output signal, format according to IEEE-754
Cycle time
min. 1 s (dependent on the parameter setting)
Sensor address
126 (default setting)
Current value
10 mA, ±0.5 mA
Damping (63 % of the input variable)
0 … 999 s, adjustable
Fulfilled NAMUR recommendations
NE
43
Resolution, digital
>
1 mm (0.039 in)
Accuracy (according to DIN EN 60770-1)
Process reference conditions according to DIN EN 61298-1
-
Temperature
+
18 … +30 °C (+64 … +86 °F)
VEGAFLEX
65 • Profibus PA
41
10 Supplement
31847
-
EN
-120329