7 Maintenance and fault rectification

VEGACAP 35 • - Relay (DPDT)

33759-EN-130916

6. Pull the cable out of the locking sleeve (4).
7. To avoid splicing of the steel cable, tin the cable before shortening

with a soldering iron and tighten the wire.

8. Shorten the cable with a cut-off wheel or a metal saw at the lower

end. Make sure the length is correct before shortening.

9. Shorten the insulation of the cable with a sharp knife by 60 mm

(2.36 in).

10. Shift the chamfered side of the locking sleeve (4) with a rotary

movement onto the cable.
Make sure that the cable is flush with the lower side of the locking

sleeve (4).

11. Lock the cable with the two pins (5).

Make sure that the cable screen has no contact to the inner steel

cable.

12. Shift the isolating sleeve (6) onto the locking sleeve (4).
13. Shift the lower part of the weight (7) to the upper part of the

weight (1) and screw them together.

14. Lock the upper part of the weight (1) with pin (8).
15. Check the correct length of the probe.
16. Carry out a fresh adjustment. See chapter "Set up, new adjust-

ment".

7.5 How to proceed in case of repair

You can find a repair form as well as detailed information on how to

proceed under www.vega.com/downloads and "Forms and certifi-

cates".
By doing this you help us carry out the repair quickly and without hav-

ing to call back for needed information.
If a repair is necessary, please proceed as follows:

Print and fill out one form per instrument

Clean the instrument and pack it damage-proof

Attach the completed form and, if need be, also a safety data

sheet outside on the packaging

Please contact for the return shipment the agency serving you. You

can find the agency on our home page www.vega.com.