4 Mounting

PLICSRADIO C62 • Wireless processing unit for PLICSRADIO T62

32627-EN-130701

4 Mounting

4.1 General instructions

Each series 600 instrument consists of the actual signal conditioning

instrument as well as a plug-in socket for carrier rail mounting (top-

hat rail 35 x 7.5 according to DIN EN 50022/60715). Because it has

protection class IP 30 or IP 20, the instrument is intended to be used

in switching cabinets.

4.2 Mounting instructions

The plug-in socket is designed for carrier rail mounting. The operat-

ing voltage is connected to terminals 17 and 18. For neighbouring

series 600 instruments it is possible to continue connection L1 and

N directly via the supplied bridges. Max. five instruments can be con-

nected through in this way.
Danger:

Looping through via bridges is only allowed for operating voltage

(sockets L1 and N). The bridges must never be used with single

instruments, at the end of a row of instruments or with other sockets.

If this rule is not heeded, there is a danger of coming into contact with

the operating voltage or causing a short circuit.

All signal conditioning instruments are provided with different gaps

dependent on type and version (mechanical coding).
The plug-in socket is provided with coded pins that can be inserted to

prevent accidental interchanging of the various instrument types.

A o

B o

C o

1 o

2 o

3 o

o

o

o

7 o

8 o

9 o

o

o

12 o

N

L1

VEGA

A o

B o

C o

1 o

2 o

3 o

4 o

5 o

6 o

7 o

8 o

9 o

10 o

11 o

12 o

N

L1

VEGA

1 2

3 4

5 6

7 8

2

2

1

Fig. 4: Plug-in socket PLICSRADIO C62
1 Type coding for PLICSRADIO C62

2 Bridges for looping the operating voltage

Installation possibilities