13

5 Connecting to power supply

PLICSRADIO C62 • Wireless processing unit for PLICSRADIO T62

32627-EN-130701

5 Connecting to power supply

5.1 Preparing the connection

Always keep in mind the following safety instructions:

Connect only in the complete absence of line voltage

If overvoltage surges are expected, overvoltage arresters should

be installed

The voltage supply can be 20 … 253 V AC/DC, 50/60 Hz.

The operating voltage of PLICSRADIO C62 is connected with stand-

ard cable according to the national installation standards.
The connection PLICSRADIO R62 - C62 is carried out with standard

two-wire cable with screen
Use cable with round cross-section. A cable outer diameter of

5 … 9 mm (0.2 … 0.35 in) ensures the seal effect of the cable gland.

If you are using cable with a different diameter or cross-section,

exchange the seal or use a suitable cable gland.

5.2 Connection procedure

Move on to electrical connection and proceed as follows:
1. Snap the socket without PLICSRADIO C62 onto the carrier rail
2. Connect the connection cable to PLICSRADIO C62
3. When using several sockets, loop the power supply by means of

bridges

4. Connect power supply (switched off) to terminal 17 and 18
5. If necessary, connect relays or other outputs
6. Insert PLICSRADIO C62 into the plug-in socket and screw it

down tightly

The electrical connection is hence finished.