6 Setup with the integrated display and adjustment unit

PLICSRADIO C62 • Wireless processing unit for PLICSRADIO T62

32627-EN-130701

The simulation of a measured value is used to check the outputs and

connected components. The simulation can be applied to the percent-

age value, the lin. percentage value and the sensor value.
Note:

Please note that connected system parts (valves, pumps, motors,

control systems) are influenced by the simulation, thus unintentional

plant operating conditions can occur. The simulation is terminated

automatically after approxminately 10 minutes.

Carry out your settings via the appropriate keys and save with

[OK].

There are two reset modes:

Reset to default: with only a few exceptions, all settings will be

reset to default. Exceptions are: Host name, IP-addr., subnet

mask, time, language.

Reset on measurement loop: The settings of the selected meas-

urement loop will be set to default. The measurement loop is

deactivated and the TAG name reset to default.

With instrument versions with integrated RS232/Ethernet interface,

a manual data transmission to a WEB-VV server can be trigger, for

example, for test purposes. Requirement is that a WEB-VV event was

configured in advance via PACTware/DTM.

In the menu item "Info" the following information is available:

Sensor type and serial number

Date of manufacture and software version

Date of last change using PC

Instrument features

MAC address (with interface option Ethernet)

Service - Simulation

Service - Reset

Service - Data transmis-

sion

Info