VEGA VEGABAR 55 Foundation Fieldbus - climate compensated User Manual

Page 48

Advertising
background image

48

10 Supplement

VEGABAR 55 • Foundation Fieldbus - climate compensated

39443-EN-130321

Nominal range

Overload capacity, max.

pressure

Overload capacity, min. pres-

sure

0 … +150 psig

+700 psig

-15 psig

0 … +350 psig

+700 psig

-15 psig

-15 … 0 psig

+500 psig

-15 psig

-15 … +25 psig

+700 psig

-15 psig

-15 … +70 psig

+700 psig

-15 psig

-15 … +150 psig

+700 psig

-15 psig

-15 … +350 psig

+700 psig

-15 psig

-0.7 … +0.7 psig

+200 psig

-15 psig

-1.5 … +1.5 psig

+290 psig

-15 psig

-3 … +3 psig

+430 psig

-15 psig

-7 … +7 psig

+500 psig

-15 psig

Reference conditions and actuating variables (according to DIN EN 60770-1)
Reference conditions according to DIN EN 61298-1

Ʋ Temperature

18 … 30 °C (64 … 86 °F)

Ʋ Relative humidity

45 … 75 %

Ʋ Air pressure

860 … 1060 mbar/86 … 106 kPa (12.5 … 15.4 psi)

Determination of characteristics

limit point adjustment according to DIN 16086

Characterstic curve

Linear

Reference installation position

upright, diaphragm points downward

Influence of the installation position

< 5 mbar/0.5 kPa (0.07 psig)

Deviation determined according to the limit point method according to IEC 60770

10)

Applies to the digital signal output (HART, Profibus PA, Foundation Fieldbus) as well as to ana-

logue current output 4 … 20 mA and refers to the set span. Turn down (TD) is the ratio nominal

measuring range/set span.
Deviation with version 0.075 %

Ʋ Turn down 1 : 1 up to 5 : 1

< 0.075 %

Ʋ Turn down > 5 : 1

< 0.015 % x TD

Deviation with version 0.1 %

Ʋ Turn down 1 : 1 up to 5 : 1

< 0.1 %

Ʋ Turn down > 5 : 1

< 0.02 % x TD

Deviation with version 0.2 %

Ʋ Turn down 1 : 1 up to 5 : 1

< 0.2 %

Ʋ Turn down > 5 : 1

< 0.04 % x TD

Deviation with absolute pressure measuring range 0.1 bar

Ʋ Turn down 1 : 1 up to 5 : 1

< 0.25 %

Ʋ Turn down > 5 : 1

< 0.05 % x TD

10)

Incl. non-linearity, hysteresis and non-repeatability.