20

5 Connecting to power supply

VEGABAR 67 • Profibus PA - climate compensated

39445-EN-130321

5 Connecting to power supply

5.1 Preparing the connection

Always keep in mind the following safety instructions:

Connect only in the complete absence of line voltage

If voltage surges are expected, overvoltage arresters should be

installed according to Profibus specifications

Tip:

We recommend VEGA overvoltage arrester B63-32.
In hazardous areas you must take note of the respective regulations,

conformity and type approval certificates of the sensors and power

supply units.

Power is supplied via a Profibus DP/PA segment coupler or a VEGA-

LOG 571 EP input card. The power supply range can differ depending

on the instrument version.
The data for power supply are specified in chapter "Technical data".

Connection is made with screened cable according to the Profibus

specification. Power supply and digital bus signal are carried over the

same two-wire connection cable.
Use cable with round cross-section. A cable outer diameter of

5 … 9 mm (0.2 … 0.35 in) ensures the seal effect of the cable gland.

If you are using cable with a different diameter or cross-section,

exchange the seal or use a suitable cable gland.
Please make sure that your installation is carried out according to the

Profibus specification. In particular, make sure that the termination of

the bus is done with appropriate terminating resistors.

On the instrument with cable entry ½ NPT and plastic housing there is

a metallic ½" threaded insert moulded into the plastic housing.
Caution:

No grease should be used when screwing the NPT cable gland or

steel tube into the threaded insert. Standard grease can contain

additives that corrode the connection between threaded insert and

housing. This would influence the stability of the connection and the

tightness of the housing.

With systems with potential equalisation, connect the cable screen

directly to ground potential at the power supply unit, in the connection

box and at the sensor. The screen in the sensor must be connected

directly to the internal ground terminal. The ground terminal outside

on the housing must be connected to the potential equalisation (low

impedance).
In systems without potential equalisation, connect the cable screen

directly to ground potential at the power supply unit and at the sensor.

In the connection box or T-distributor, the screen of the short stub to

the sensor must not be connected to ground potential or to another

cable screen. The cable screens to the power supply unit and to the

Safety instructions

Voltage supply

Connection cable

Cable gland ½ NPT

Cable screening and

grounding