10 Supplement

VEGABAR 67 • Profibus PA - climate compensated

39445-EN-130321

Status

code

Description according to

Profibus standard

Possible cause

0 x 4c

uncertain - initial value

Failsafe replacement value (Failsafe-Mode = "Last valid value" and

no valid measured value since switching on)

0 x 51

uncertain - sensor; conversion

not accurate - low limited

Sensor value < lower limit

0 x 52

uncertain - sensor; conversion

not accurate - high limited

Sensor value > upper limit

0 x 80

good (non-cascade) - OK

OK

0 x 84

good (non-cascade) - active

block alarm

Static revision (FB, TB) changed (10 sec. active, after the parame-

ter of the static category has been written)

0 x 89

good (non-cascade) - active ad-

visory alarm - low limited

Lo-Alarm

0 x 8a

good (non-cascade) - active ad-

visory alarm - high limited

Hi-Alarm

0 x 8d

good (non-cascade) - active crit-

ical alarm - low limited

Lo-Lo-Alarm

0 x 8e

good (non-cascade) - active crit-

ical alarm - high limited

Hi-Hi-Alarm

10.3 Dimensions

The following dimensional drawings represent only an extract of the possible versions. Detailed

dimensional drawings can be downloaded on www.vega.com under "Downloads" and "Drawings".

Plastic housing

~ 69 mm

(2.72")

ø 79 mm

(3.03")

112 mm (4.41"

)

M20x1,5/

½ NPT

~ 84 mm (3.31")

M16x1,5

112 mm (4.41"

)