VEGA VEGABAR 67 Profibus PA - climate compensated User Manual

Page 55

Advertising
background image

55

10 Supplement

VEGABAR 67 • Profibus PA - climate compensated

39445-EN-130321

Nominal range

Overload capacity, max.

pressure

Overload capacity, min. pres-

sure

0 … +900 psig

+2900 psig

-15 psig

Reference conditions and actuating variables (according to DIN EN 60770-1)
Reference conditions according to DIN EN 61298-1

Ʋ Temperature

18 … 30 °C (64 … 86 °F)

Ʋ Relative humidity

45 … 75 %

Ʋ Air pressure

860 … 1060 mbar/86 … 106 kPa (12.5 … 15.4 psi)

Determination of characteristics

limit point adjustment according to DIN 16086

Characterstic curve

Linear

Reference installation position

upright, diaphragm points downward

Influence of the installation position

< 5 mbar/0.5 kPa (0.07 psig)

Deviation determined according to the limit point method according to IEC 60770

11)

Applies to the digital signal output (HART, Profibus PA, Foundation Fieldbus) as well as to ana-

logue current output 4 … 20 mA and refers to the set span. Turn down (TD) is the ratio nominal

measuring range/set span.
Deviation

Ʋ Turn down 1 : 1 up to 5 : 1

< 0.1 %

Ʋ Turn down > 5 : 1

< 0.02 % x TD

Influence of the product or ambient temperature
Average temperature coefficient of the zero signal and the output span
Applies to the digital signal output (HART, Profibus PA, Foundation Fieldbus) as well as to ana-

logue current output 4 … 20 mA and refers to the set span. Turn down (TD) is the ratio nominal

measuring range/set span.

Nominal measuring range

in bar/kPa

Nominal measuring

range in psig

Average temperature co-

efficient of the zero signal

and the output span, in

the compensated temper-

ature range 0 … +100 °C

(+32 … +212 °F), refer-

ence temperature 20 °C

(68 °F)

Average temperature co-

efficient of the zero signal

and the output span, out-

side the compensated

temperature range

0 … 0.2 bar/0 … 20 kPa

0 … 3 psi

< (0.15 + 0.4 x TD)%

< (0.15 + 0.6 x TD)%

0 … 0.4 bar/0 … 40 kPa

0 … 6 psig

< (0.15 + 0.4 x TD)%

< (0.15 + 0.6 x TD)%

0 … 1 bar/0 … 100 kPa

0 … 15 psig

< (0.1 + 0.2 x TD)%

< (0.1 + 0.3 x TD)%

0 … 2.5 bar/0 … 250 kPa

0 … 35 psig

< (0.1 + 0.2 x TD)%

< (0.1 + 0.3 x TD)%

0 … 5 bar/0 … 500 kPa

< (0.05 + 0.1 x TD)% < (0.1 + 0.15 x TD)%

0 … 10 bar/0 … 1000 kPa

0 … 150 psig

< (0.05 + 0.1 x TD)% < (0.1 + 0.15 x TD)%

0 … 25 bar/0 … 2500 kPa

0 … 350 psig

< (0.05 + 0.1 x TD)% < (0.1 + 0.15 x TD)%

Thermal change of the current output
Applies also to the analogue 4 … 20 mA current output and refers to the set span.

11)

Incl. non-linearity, hysteresis and non-repeatability.