VEGA VEGAPULS SR 68 4 … 20 mA_HART - four-wire User Manual

Page 43

Advertising
background image

43

6 Set up with the display and adjustment module

VEGAPULS SR 68 • 4 … 20 mA/HART - four-wire

38295-EN-130624

Enter the requested parameters via the appropriate keys, save your

settings with [OK] and jump to the next menu item with the [ESC] and

the [->] key.

Since the radar sensor is a distance measuring instrument, the

distance from the sensor to the product surface is measured. For

indication of the real level, an allocation of the measured distance to

the percentage height must be carried out.
To perform the adjustment, enter the distance with full and empty ves-

sel, see the following example:

2

1

100%

0%

1 m

(39.37

")

35 m (1378

")

Fig. 33: Parameter adjustment example min./max. adjustment
1 Min. level = max. meas. distance

2 Max. level = min. meas. distance

If these values are not known, an adjustment with the distances of for

example 10 % and 90 % is possible. Starting point for these distance

specifications is always the seal surface of the thread or flange. By

means of these settings, the real level will be calculated.
The real product level during this adjustment is not important, be-

cause the min./max. adjustment is always carried out without chang-

ing the product level. These settings can be made ahead of time

without the instrument having to be installed.

Proceed as follows:
1. Select the menu item "Setup" with [->] and confirm with [OK].

Now select with [->] the menu item "Min. adjustment" and confirm

with [OK].

Setup - Adjustment

Setup - Min. adjustment

Advertising