9 Diagnosis, Asset Management and service

VEGAPULS SR 68 • 4 … 20 mA/HART - four-wire

38295-EN-130624

Measurement error during emptying

Fault description

Error pattern

Cause

Rectification

6. Measured value re-

mains unchanged in

the close range during

emptying

Level

time

0

– False echo larger than the level

echo

– Level echo too small

– Remove false echoes in the

close range. Check: Antenna

must protrude out of the socket

– Remove contamination on the

antenna

– Minimize interfering instal-

lations in the close range by

changing the polarization

direction

– After removing the false ech-

oes, the false signal suppres-

sion must be deleted. Carry out

a new false signal suppression

7. Measured value

jumps sporadically to-

wards 100 % during

emptying

Level

time

0

– Changing condensation or con-

tamination on the antenna

– Carry out false signal suppres-

sion or increase false signal

suppression in the close range

by editing

– With bulk solids use radar sen-

sor with purging air connection

or flexible antenna cover

8. Measured val-

ue fluctuates around

10 … 20 %

Level

time

0

– Various echoes from an uneven

product surface, e.g. an extrac-

tion funnel

– Check parameter "Medium

type" and adapt, if necessary

– Optimize installation position

and sensor orientation

– Reflections from the product

surface via the vessel wall

(deflection)

Depending on the reason for the fault and the measures taken, the

steps described in chapter "Setup" must be carried out again or must

be checked for plausibility and completeness.

Should these measures not be successful, please call in urgent cases

the VEGA service hotline under the phone no. +49 1805 858550.
The hotline is also available outside normal working hours, seven

days a week around the clock.
Since we offer this service worldwide, the support is provided in

English. The service itself is free of charge, the only costs involved are

the normal call charges.

9.5 Exchanging the electronics module

If the electronics module is defective, it can be replaced by the user.
In Ex applications only one instrument and one electronics module

with respective Ex approval may be used.
If there is no electronics module available on site, the electronics

module can be ordered through the agency serving you. The electron-

ics modules are adapted to the respective sensor and differ in signal

output or voltage supply.
The new electronics module must be loaded with the default settings

of the sensor. These are the options:

Reaction after fault recti-

fication