2 parameter adjustment with pactware – VEGA VEGABAR 55 4 … 20 mA_HART - climate compensated User Manual

Page 42

Advertising
background image

42

7 Set up with PACTware and other adjustment programs

VEGABAR 55 • 4 … 20 mA/HART - climate compensated

39441-EN-130321

1

2 4

3

OP

EN

TWIST

US

B

LOCK

Fig. 26: Connecting the PC via HART to the signal cable
1 VEGABAR 55

2 HART resistance 250 Ω (optional depending on processing)

3 Connection cable with 2 mm pins and terminals

4 Processing system/PLC/Voltage supply

Necessary components:

VEGABAR 55

PC with PACTware and suitable VEGA DTM

VEGACONNECT

HART resistance approx. 250 Ω

Power supply unit or processing system

Note:

With power supply units with integrated HART resistance (internal

resistance approx. 250 Ω), an additional external resistance is not

necessary. This applies, e. g. to the VEGA instruments VEGATRENN

149A, VEGADIS 371, VEGAMET 381. Common Ex separators are

also usually equipped with a sufficient current limitation resistance.

In such cases, VEGACONNECT 4 can be connected parallel to the

4 … 20 mA cable.

7.2 Parameter adjustment with PACTware

Further setup steps are described in the operating instructions

manual "DTM Collection/PACTware" attached to each CD and which

can also be downloaded from our homepage. A detailed description

is available in the online help of PACTware and the VEGA DTMs.
Note:

Keep in mind that for setup of VEGABAR 55, DTM-Collection in the

actual version must be used.
All currently available VEGA DTMs are included as a DTM Collection

on a CD. They can be purchased for a token fee from the responsible

VEGA agency. In addition, the actual PACTware version is also avail-

able on this CD.
In addition, this DTM Collection incl. the basic version of PACTware

can be downloaded free of charge from the Internet. Move via www.

vega.com and "Downloads" to "Software".

VEGACONNECT via HART