6 Set up with the display and adjustment module PLICSCOM

VEGABAR 51 • Foundation Fieldbus

36715-EN-130321

The actual measured value is also displayed in the menu items for

min./max. adjustment.

In this menu item you select the adjustment unit as well as the unit for

the temperature indication in the display.
To select the adjustment unit (in the example switching over from bar

to mbar), proceed as follows:

3)

1. Push the [OK] button in the measured value display, the menu

overview is displayed.

Basic adjustment
Display
Diagnostics
Service
Info

2. Confirm the menu "Basic adjustment" with [OK], the menu item

"Unit" will be displayed.

Unit
Unit of measurement
bar

Temperature unit
°C

3. Activate the selection with [OK] and select "Units of measure-

ment with [->].

4. Activate the selection with [OK] and select the requested unit with

[->] (in the example mbar).

5. Confirm with [OK] and move to position correction with [->].
The adjustment unit is thus switched over from bar to mbar.
Information:

When switching over to adjustment in a height unit (in the example

from bar to m), the density also has to be entered.
Proceed as follows:
1. Push the [OK] button in the measured value display, the menu

overview is displayed.

2. Confirm the menu "Basic adjustment" with [OK], the menu item

"Units of measurement" will be displayed.

3. Activate the selection with [OK] and select the requested unit with

[->] (in the example m).

4. Confirm with [OK], the submenu "Density unit" appears.

Unit of measurement

Density unit

kg/dm³
pcf

5. Select the requested unit, e.g. kg/dm³ with [->] and confirm with

[OK], the submenu "Density" appears.

Unit of measurement

Select unit

3)

Selection options: mbar, bar, psi, Pa, kPa, MPa, inHg, mmHg, inH

2

O,

mmH

2

O.