VEGA VEGABAR 51 Foundation Fieldbus User Manual

Page 30

Advertising
background image

30

6 Set up with the display and adjustment module PLICSCOM

VEGABAR 51 • Foundation Fieldbus

36715-EN-130321

Density
0001000
kg/dm³

6. Enter the requested density value with [->] and [+], confirm with

[OK] and move to position correction with [->].

The adjustment unit is thus switched over from bar to m.
Proceed as follows to select the temperature unit:

4)

1. Activate the selection with [OK] and select "Temperature unit

with [->].

2. Activate the selection with [OK] and select the requested unit with

[->] (e.g. °F).

3. Confirm with [OK].
The temperature unit is hence switched over from °C to °F.

Proceed as follows:
1. Activate in the menu item "Position correction" the selection with

[OK].

Position correction
Offset

P

=
+0000 mbar
53 mbar

2. Select with [->], e.g. to accept actual measured value.

Position correction
Accept current measured

value?

Accept
Edit

3. Confirm with [OK] and move to min.(zero) adjustment with [->].

Proceed as follows:
1. Edit the % value in the menu item "Min. adjustment" with [OK].

Min. adjustment
+000.0 %
=
+0000.0 mbar

0000.0 mbar

2. Set the requested percentage value with [+] and [->].
3. Confirm with [OK] and edit the requested mbar value.
4. Set the requested mbar value with [+] and [->].
5. Confirm with [+] and move to max. adjustment with [->].
The min. adjustment is finished.
Information:

For an adjustment with filling, simply enter the actual measured value

indicated at the bottom of the display.

Carry out a position cor-

rection

Carry out min. adjustment

4)

Selection options: °C, °F.

Advertising