VEGA VEGABAR 51 Foundation Fieldbus User Manual

Page 50

Advertising
background image

50

10 Supplement

VEGABAR 51 • Foundation Fieldbus

36715-EN-130321

Long-term stability (according to DIN 16086 and IEC 60770-1)
Applies to digital interfaces (HART, Profibus PA, Foundation Fieldbus) as well as to analogue cur-

rent output 4 … 20 mA. Specifications refer to the set span. Turn down (TD) = nominal measuring

range/set span.
Long-term drift of the zero signal

< (0.1 % x TD)/year

Ambient conditions
Ambient, storage and transport temperature

Ʋ Standard version

-40 … +80 °C (-40 … +176 °F)

Ʋ Version for oxygen applications

11)

-40 … +60 °C (-40 … +140 °F)

Ʋ Versions IP 66/IP 68 (1 bar) and IP 68

(25 bar), connection cable PUR

-20 … +80 °C (-4 … +176 °F)

Ʋ Version IP 66/IP 68 (1 bar), connec-

tion cable PE

-20 … +60 °C (-4 … +140 °F)

Additional temperature influence through chemical seal
The specifications refer to diaphragm material 316L as well as isolating liquid silicone oil. They are

only used for estimation. The actual values depend on the diameter, material and strength of the

diaphragm as well as the isolating liquid. They are available on request.
Temperature coefficient of the chemical seal in mbar/10 K with

Ʋ Flange DN 50 PN 40, Form C,

DIN 2501

1.2 mbar/10 K

Ʋ Flange DN 80 PN 40, Form C,

DIN 2501

0.25 mbar/10 K

Ʋ Flange DN 80 PN 40, Form C,

DIN 2501 with extension 50 mm

1.34 mbar/10 K

Ʋ Flange 2" 150 lbs RF, ANSI B16.5

1.2 mbar/10 K

Ʋ Flange 3" 150 lbs RF, ANSI B16.5

0.25 mbar/10 K

Ʋ Flange 3" 150 lbs RF, ANSI B16.5 with

extension 2 "

1.34 mbar/10 K

Temperature coefficient of a cooling ele-

ment, depending on the diaphragm-ø

0.1 … 1.5 mbar/10 K

Temperature coefficient of a 1 m

long capillary line, depending on the

diaphragm-ø

0.1 … 15 mbar/10 K

Process conditions
The specifications of the pressure stage and product temperature are used as an overview. The

specifications on the type label are applicable.
Pressure stages

Ʋ Thread

PN 160 … PN 600

Ʋ Flanges

PN 16 … PN 100

Ʋ Hygienic fittings

PN 16 … PN 40

11)

Up to 60 °C (140 °F).

Advertising