4 installation position – VEGA VEGADIF 65 Chemical seal CSB User Manual

Page 11

Advertising
background image

11

3 Planning instructions for isolating systems

Chemical seal CSB • for VEGADIF 65

36133-EN-130417

90 %

100 %

t

T90%

1

2

Fig. 9: Presentation of the step response time (T90)
1 Pressure jump

2 Output signal

For minimisation of the step response time, you have to following

options:

Bigger capillary inner diameter

Shorter capillaries

Filling oil with lowest viscosity

3.4 Installation position

When the pressure transmitter is mounted above the lower chemical

seal, the max. height difference H1 according to the following illustra-

tion may not be exceeded. The value depends on the density of the

filling oil and the smallest pressure that may act on the chemical seal

of the plus side (empty vessel).
Typical values for H1 are 7 m with silicone oil and 4 m with halocarbon

oil.

+ –

+

H1

+

Fig. 10: Max. height when mounting above the lower chemical seal

In vacuum applications, the pressure transmitter should be mounted

at the same height as or below the lower chemical seal. By doing

Minimization of the step

response time

Standard applications

Vacuum applications