13

3 Planning instructions for isolating systems

Chemical seal CSB • for VEGADIF 65

36133-EN-130417

3.5 Selection of the measuring range

For instruments with chemical seals and capillaries, the zero point

shift due to the hydrostatic pressure of the fluid column in the capillar-

ies must be taken into account when selecting the measuring cell.

+ –

+

min.

ρ

M

= 0,96 kg/dm

3

= 1,0 kg/dm

3

p

i

ρ

Fl

H1 = 0,3 m

Hv = 1,8 m

H = 1 m

Hu = 0,2 m

max.

Fig. 14: Data for selection of the measuring cell

Pressure on the minus side of the differential pressure trans-

mitter with min. level:

p

-

= p

Hv

+ p

H1

= Hv • ρ

Fl

• g + H1 • ρ

Fl

•g+ p

i

= 1.8 m • (0.96 kg/dm³ • 9.81 m/s) + 0.3 m • (0.96 kg/dm³ • 9.81m/s)

+ p

i

= 197.77 mbar + p

i

Pressure on the plus side of the differential pressure transmit-

ter with min. level:

p

+

=p

Hu

+ p

H1

= Hu •ρ

FM

• g + H1 •ρ

Fl

•g+p

i

= 0.2 m • (1 kg/dm³ • 9.81 m/s) + 0.3 m • (0.96 kg/dm³ • 9.81 m/s) +p

i

= 47.87 mbar + p

i

Differential pressure on the transmitter with min. level:

Δp

Transmitter

= p

+

- p

-

= 47.87 mbar - 197.77 mbar
= -149.90 mbar
Differential pressure on the transmitter with max. level:

Δp

Transmitter

= p

+

- p

-

+ΔH •(1.0 kg/dm³ • 9.81 m/s)

= -149.90 mbar + 98.1 mbar

Example for selection of

the measuring cell