VEGA VEGADIF 65 Chemical seal CSB User Manual

Page 14

Advertising
background image

14

3 Planning instructions for isolating systems

Chemical seal CSB • for VEGADIF 65

36133-EN-130417

= -51.80 mbar
Hence a 100 mbar measuring cell is required for this application

example.

3.6 Calculation of the temperature error

With double-sided mounting of chemical seals, the total temperature

influence is composed of the following:

Influence of the process temperature on the chemical seal

(TK

Process

)

Corrective factor with special materials (with Tantalum, Hastelloy:

1.5; with PTFE coating: 1.8)

Corrective factor for filling oil

Influence of the ambient temperature on the transmitter (TK

Ambient

)

The calibration temperature of the isolating system is 20 °C.
The TK

Process

of the respective chemical seal is listed in the charts in

chapter "Dimensions and weights". The corrective factor with special

materials is available on request. The corrective factor for the filling

oil is listed in chapter "Filling oils". The thermal change of zero signal

and span is specified in chapter "Technical data" of VEGADIF 65. The

calculated influencing factors must be summed geometrically.

Process temperature: 100 °C

Flange isolating diaphragm DN 80 PN 10-40

Capillary length: 4 m

Filing oil silicone, correction factor 1

Diaphragm material.: Tantalum, correction factor 1.5

Ambient temperature TU: 40 °C

TK

chemical seal

= 0.3 mbar/10K

ΔT Process temperature-Reference temperature chemical seal

= 100 °C - 20 °C = 80 K
Number of chemical seals = 2
Corrective factor diaphragm material = 1.5
Error calculation
Δp

chemical seal

= (0.3 mbar/10K) • 80K = 2.4 mbar • 2 = 4.8 mbar

= 4.8 mbar • 1,5 = 7.2 mbar
With double-sided mounting of chemical seals, the total temperature

influence is 7.2 mbar

Example of double-sided

chemical seal:

Advertising