VEGA VEGAPULS 68 (≥ 2.0.0 - ≥ 4.0.0) 4 … 20 mA_HART - two-wire User Manual

Page 17

Advertising
background image

17

4 Mounting

VEGAPULS 68 • 4 … 20 mA/HART - two-wire

36535-EN-130205

200 mm

(7.87")

Fig. 8: Mounting of the radar sensor on the vessel top

If you cannot keep this distance you should carry out a false echo sto-

rage before setup. This applies mainly if buildup on the vessel wall is

expected. In this case, we recommend repeating a false echo storage

later with existing buildup.

Mounting should not be too close to the inflowing material as the

microwave signal will be interferred. The optimum mounting position is

on the opposite of the filling. To avoid strong pollution, the distance to

the filter or dust extraction must be as big as possible.

Fig. 9: Mounting of the radar sensor with inflowing medium

With bulk solids silos with lateral pneumatic filling, mounting should

not be in the filling stream as the microwave signal will be interferred.

The optimum mounting position is next to the filling. To avoid strong

pollution, the distance to the filter or dust extraction must be as big as

possible.

Inflowing medium

Advertising