9 Diagnosis, Asset Management and service

VEGAPULS 68 • 4 … 20 mA/HART - two-wire

36535-EN-130205

Measurement error during emptying

Fault description

Error pattern

Cause

Rectification

6th measured value re-

mains unchanged in

the close range during

emptying

Level

time

0

– False echo larger than the level

echo

– Level echo too small

– Remove false echoes in the

close range. Check: Antenna

must protrude out of the socket

– Remove contamination on the

antenna

– Minimize interfering installati-

ons in the close range by chan-

ging the polarization direction

– After removing the false

echoes, the false signal

suppression must be deleted.

Carry out a new false signal

suppression

7th measured value

jumps sporadically to-

wards 100 % during

emptying

Level

time

0

– Varying condensation or conta-

mination on the antenna

– Carry out false signal suppres-

sion or increase false signal

suppression in the close range

by editing

– With bulk solids use radar sen-

sor with purging air connection

or flexible antenna cover

8th measured va-

lue fluctuates around

10 … 20 %

Level

time

0

– Various echoes from an uneven

product surface, e.g. an extrac-

tion funnel

– Check application parameter

"Medium type" and adapt, if

necessary

– Optimize installation position

and sensor orientation

– Reflections from the product

surface via the vessel wall

(deflection)

Depending on the reason for the fault and the measures taken, the

steps described in chapter "Setup" must be carried out again or must

be checked for plausibility and completeness.

Should these measures not be successful, please call in urgent cases

the VEGA service hotline under the phone no. +49 1805 858550.
The hotline is also available outside the normal working hours on

seven days a week around the clock.
Since we offer this service worldwide, the support is in the English

language. The service itself is free of charge, the only costs involved

are the normal call charges.

9.5 Exchanging the electronics module

If the electronics module is defective, it can be replaced by the user.
In Ex applications only one instrument and one electronics module

with respective Ex approval may be used.
If there is no electronics module available on site, the electronics mo-

dule can be ordered through the agency serving you. The electronics

modules are adapted to the respective sensor and differ in signal

output or voltage supply.
The new electronics module must be loaded with the default settings

of the sensor. These are the options:

Reaction after fault recti-

fication

24 hour service hotline