11 Supplement

VEGAPULS 68 • 4 … 20 mA/HART - two-wire

36535-EN-130205

Input variable
Measured variable

The measured quantity is the distance between process

fitting of the sensor and product surface. The reference

plane is the seal surface on the hexagon or the lower

side of the flange.

3

4

2

1

Fig. 53: Data of the input variable
1 Reference plane

2 Measured variable, max. measuring range

3 Antenna length

4 Useful measuring range

Max. measuring range

75 m (246.1 ft)

Recommended meas. range depending on the antenna diameter

Ʋ ø 40 mm (1.575 in)

up to 15 m (49.21 ft)

Ʋ ø 48 mm (1.89 in)

up to 20 m (65.62 ft)

Ʋ ø 75 mm (2.953 in)

up to 40 m (131.2 ft)

Ʋ ø 95 mm (3.74 in)

up to 50 m (164 ft)

Ʋ Parabolic antenna

up to 75 m (246.1 ft)

Output variable
Output signal

4 … 20 mA/HART

Fulfilled HART specification

7.0

Signal resolution

0.3 µA

Failure signal current output (adjustable) mA-value unchanged 20.5 mA, 22 mA, < 3.6 mA
Max. output current

22 mA

Starting current

≤ 3.6 mA; ≤ 10 mA for 5 ms after switching on

Load

see load diagram under Power supply

Damping (63 % of the input variable),

adjustable

0 … 999 s

HART output values according to HART 7.0

1)

Ʋ PV (Primary Value)

Distance to the level

1)

Default values, can be assigned individually