VEGA VEGABAR 87 Save sensor - Operating Instructions User Manual

Page 10

Advertising
background image

10

3 Product description

VEGABAR 87 • Slave sensor for electronic differential pressure

45053-EN-131011

4

3

2

1

Fig. 3: Configuration of the METEC

®

measuring cell with VEGABAR 87

1 Process diaphragm

2 Isolating liquid

3 FeNi adapter

4 CERTEC

®

measuring cell

The measuring cell design depends on the selected pressure type.

Relative pressure: the measuring cell is open to atmosphere. The

ambient pressure is detected in the measuring cell and compensated.

It thus has no influence on the measured value.
Absolute pressure: the measuring cell is evacuated and encapsu-

lated. The ambient pressure is not compensated and does hence

influence the measured value.
Relative pressure, climate-compensated: the measuring cell is

evacuated and encapsulated. The ambient pressure is detected

through a reference sensor in the electronics and compensated. It

thus has no influence on the measured value.

The process pressure acts on the sensor element via the stainless

steel diaphragm and an internal transmission liquid. The process

pressure causes a resistance change which is converted into a cor-

responding output signal and outputted as measured value.
The METEC

®

measuring cell is the measuring unit. It consists of

the ceramic-capacitive CERTEC

®

measuring cell and a special,

temperature-compensated isolating system.

Pressure types

Measuring system

Advertising