4 Mounting

VEGABAR 87 • Slave sensor for electronic differential pressure

45053-EN-131011

1

2

3

4

4

4

Fig. 6: Position of the filter element - non-Ex, Ex-ia version
1 Housing plastic, stainless steel precision casting

2 Housing aluminium

3 Housing stainless steel, electropolished

4 Filter element

With the following instruments a blind plug is installed instead of the

filter element:

Instruments in protection IP 66/IP 68 (1 bar) - ventilation via capil-

laries in fix connected cable

Instruments with absolut pressure

The filter element is mounted into the electronics housing. It has the

following functions:

Ventilation electronics housing

Atmospheric pressure compensation (with relative pressure meas-

uring ranges)

1

Fig. 7: Position of the filter element - IP 69K version
1 Filter element

Instruments with absolute pressure have a blind plug mounted

instead of the filter element.

4.3 Combination Master - Slave

In principle, any sensor combination within the VEGABAR 80 series is

allowed. The following requirements must be fulfilled:

Configuration, Master sensor suitable for electronic differential

pressure

Pressure type is identical for both sensors, i.e. relative pressure/

relative pressure or absolute pressure/absolute pressure

The master sensor must always measure the higher pressure

Measurement setup as shown in the following chapters