VEGA VEGABAR 87 Save sensor - Operating Instructions User Manual

Page 33

Advertising
background image

33

6 Set up with the display and adjustment module

VEGABAR 87 • Slave sensor for electronic differential pressure

45053-EN-131011

Proceed as follows:
1. Select with [->] the menu item "Span adjustment" and confirm

with [OK].

2. Edit the mbar value with [OK] and set the cursor to the requested

position with [->].

3. Set the requested mbar value with [+] and store with [OK].
The span adjustment is finished.
For an adjustment with pressure, simply enter the actual measured

value indicated at the bottom of the display.

Proceed as follows:
1. Select the menu item "Setup" with [->] and confirm with [OK].

Now select with [->] the menu item "Distance" and confirm with

[OK].

2. Edit the sensor distance with [OK] and set the cursor to the

requested position with [->].

3. Set the requested distance with [+] and store with [OK].
The adjustment of the distance is hence finished.

Proceed as follows:
1. Select the menu item "Setup" with [->] and confirm with [OK].

Now select with [->] the menu item "Min. adjustment" and confirm

with [OK].

2. Edit the percentage value with [OK] and set the cursor to the

requested position with [->].

3. Set the requested percentage value with [+] and save with [OK].

The cursor jumps now to the density value.

4. Enter the min. distance suitable for the percentage value.
5. Save settings with [OK] and move with [ESC] and [->] to the max.

adjustment.

The min. adjustment for density is finished.

Proceed as follows:

Setup - span adjustment,

differential pressure

Setup - Distance, density

Setup - Min. adjustment,

density

Setup - Max. adjustment,

density

Advertising