4 mounting, 1 general instructions to use the instrument – VEGA VEGABAR 87 Save sensor - Operating Instructions User Manual

Page 13

Advertising
background image

13

4 Mounting

VEGABAR 87 • Slave sensor for electronic differential pressure

45053-EN-131011

4 Mounting

4.1 General instructions to use the instrument

Make sure that all parts of the instrument exposed to the process are

suitable for the existing process conditions.
These are mainly:

Active measuring component

Process fitting

Process seal

Process conditions are particularly:

Process pressure

Process temperature

Chemical properties of the medium

Abrasion and mechanical influences

You can find the specifications of the process conditions in chapter

"Technical data" as well as on the nameplate.

Protect your instrument further through the following measures

against moisture penetration:

Use the recommended cable (see chapter "Connecting to power

supply")

Tighten the cable gland

Loop the connection cable downward in front of the cable gland

This applies particularly to:

Outdoor mounting

Installations in areas where high humidity is expected (e.g. through

cleaning processes)

Installations on cooled or heated vessels

On instruments with process fitting thread, the hexagon must be tight-

ened with a suitable screwdriver. Wrench size see chapter "Dimen-

sions".

Warning:

The housing must not be used to screw the instrument in! Applying

tightening force can damage internal parts of the housing.

In case of strong vibrations at the mounting location, the instrument

version with external housing should be used. See chapter "External

housing".

Higher process temperatures often mean also higher ambient

temperatures. Make sure that the upper temperature limits stated in

chapter "Technical data" for the environment of the electronics hous-

ing and connection cable are not exceeded.

Suitability for the process

conditions

Protection against mois-

ture

Screwing in

Vibrations

Temperature limits

Advertising