7 Set up with the display and adjustment module

MINITRAC 31 • 4 … 20 mA/HART - four-wire

43389-EN-131119

After a change, all safety-relevant parameters must be verified. For

this purpose, a character string comparison must be carried out. This

is used to check the character respresentation and the communica-

tion channels.
Confirm if the two character strings are identical. The verification texts

are provided in German and with all other menu languages in English.

In a second step, all modified safety-relevant parameters are listed.

Confirm the modified values.

If the described process of parameter adjustment was run through

completely and correctly, the instrument will be locked and hence

ready for operation.

Otherwise the instrument remains in the released and hence unsafe

condition.

The main menu is divided into five sections with the following func-

tions:

Setup: Settings, e.g. for measurement loop name, isotope, applica-

tion, background radiation, adjustment, signal output
Display: Settings, for example language, measured value display
Diagnosis: Information, for example, of device status, peak value,

simulation
Additional adjustments: Instrument unit, reset, date/time, copying

function
Info: Instrument name, hardware and software version, date of manu-

facture, instrument features

Check if the correct language is already set for the display. If not, you

can change the language in the menu item "Display/Language".

Main menu

Procedure