7 Set up with the display and adjustment module

MINITRAC 31 • 4 … 20 mA/HART - four-wire

43389-EN-131119

The following table shows the default values of the instrument. The

values apply for the application "Level". First of all you have to select

the application.
Depending on the instrument version, not all menu items may be

available or they may be differently assigned:

Menu

Menu item

Default value

Setup

Measurement

loop name

Sensor

Isotope

Cs-137

Application

Limit level

Adjustment mode Single point adjustment
Adjustment - un-

covered

90000 ct/s

Adjustment - cov-

ered

9000 ct/s
only with two-point adjustment

Delta I

90 %

Background ra-

diation

0 ct/s

Temperature unit °C
Damping

Is calculated automatically by the in-

strument

Current output

mode

8/16 mA, < 3.6 mA

Mode - Relay

Overfill protection

Block adjustment Released

Display

Language

Selected language

Displayed value

Pulse rate

Additional adjust-

ments

Temperature unit °C
HART mode

Standard

With this function you can select the mode.

The sensor offers the HART modes standard and multidrop.
If the measured value is outputted via the 4 … 20 mA output, you

must not switch over to HART Multidrop.
The mode 'Standard', with fixed address 0 (factory setting), means

output of the measured value as 8/16 mA signal.
This parameter is described in the operating instructions manual

"Display and adjustment module".

With this function

Load parameter adjustment data from the sensor into the display

and adjustment module

Write parameter adjustment data from the display and adjustment

module into the sensor

Additional adjustments -

HART mode

Additional adjustments -

Copy instrument settings