VEGA VEGAPULS 65 (≥ 2.0.0 - ≥ 4.0.0) Modbus and Levelmaster protocol User Manual

Page 51

Advertising
background image

51

11 Supplement

VEGAPULS 65 • Modbus and Levelmaster protocol

41365-EN-121011

3

4

2

1

Fig. 26: Data of the input variable
1 Reference plane

2 Measured variable, max. measuring range

3 Antenna length

4 Useful measuring range

Max. measuring range

35 m (114.83 ft)

Recommended measuring range

up to 10 m (32.81 ft)

Output variable
Output

Ʋ Physical layer

Digital output signal according to standard EIA-485

Ʋ Bus specifications

Modbus Application Protocol V1.1b, Modbus over serial

line V1.02

Ʋ Protocols

Modbus RTU, Modbus ASCII, Levelmaster

Max. transmission rate

9.6 Kbit/s

Accuracy (according to DIN EN 60770-1)
Process reference conditions according to DIN EN 61298-1

Ʋ Temperature

+18 … +30 °C (+64 … +86 °F)

Ʋ Relative humidity

45 … 75 %

Ʋ Air pressure

860 … 1060 mbar/86 … 106 kPa (12.5 … 15.4 psig)

Installation reference conditions

Ʋ Min. distance to installations

> 200 mm (7.874 in)

Ʋ Reflector

Plane plate reflector

Ʋ False reflections

Largest false echo 20 dB smaller than the useful echo

Deviation with liquids

See following diagrams